Vitodens Rigid and Flex Venting Systems Installation
Single Pipe Venting (Room Air Dependent)
Vent Length Requirements
Maximum vent pipe length - horizontal
All PP(s) vent material and air intake (if PP(s) used) must
be ULC S636 or UL 1738 listed, manufactured by M&G /
DuraVent or Centrotherm InnoFlue.
Size the exhaust vent pipe as specified in the table below.
This table lists the maximum allowable vent length in feet
and meters of the exhaust piping. Vent diameter must not
be reduced at any point in the installation.
First elbow not included in equivalent vent calculation.
Always include vent termination length in calculations.
IMPORTANT
Maximum allowable equivalent length - horizontal
Boiler Model
System Ø
Max. equivalent vent length ”a”
*
3
WB1B 26, 35
2 in. (51 mm)*1
3 in. (76 mm)*2
4 in. (102 mm)*2
86 ft. (31 m)
164 ft. (50 m)
200 ft. (61 m)
WB2B 19, 26, 35, B2HA 19, 28, 35, B2TA 19, 35,
B2HB 19, 26, 35, B2TB 19, 35
2 in. (51 mm)*1
3 in. (76 mm)*2
4 in. (102 mm)*2
115 ft. (35 m)
148 ft. (45 m)
180 ft. (55 m)
WB2B 45, 60, B2HA 45, 60, B2HB 45, 57
3 in. (76 mm)
4 in. (102 mm)*2
98 ft. (30 m)
148 ft. (45 m)
WB2B 80, 105, B2HA 80, 88, 100, 112
4 in. (102 mm)
131 ft. (40 m)
B2HA 150
4 in. (100 mm)*4
5 in. (125 mm)*5
131 ft. (40 m)
131 ft. (40 m)
*1
2 in. diameter system only available with CPVC / PP(s) system
*2
4 in. (3 in. to 4 in. increaser field supplied).
*3
See illustration below.
*
4
Due to higher exhaust vent pipe resistance, there is an automatic input reduction of 9% for model B2HA 150
when a 4 inch diameter vent pipe is used.
*
5
4 in. to 5 in. increaser field supplied.
Minimum vent length is 3.3 ft. (1 m).
For PP(s) systems, all exhaust vent and air intake piping
and elbows exposed outside, must be UV resistant
polypropylene (supplied by the vent manufacturer).
IMPORTANT
Vitodens 100-W WB1B 26, 35,
Vitodens 222-F B2TA 19, 35,
Vitodens 222-F B2TB 19, 35,
Vitodens 200-W WB2B 19, 26, 35
Vitodens 200-W B2HA 19, 28, 35,
Vitodens 200-W B2HB 19, 26, 35,
A
C
C
B
Flue
a
Side wall
Flue starter adaptor - Stainless Steel & CPVC (all boilers)
- PP(s) (WB2B 80, 105, B2HA 80, 88, 100, 112, 150
only)
Caulk here
(exterior caulking)
D
Legend
A
Support system
B
Exhaust vent termination
C
Combustion air intake (left, right or through co-axial
opening), remove and discard air intake cover
(WB1B 26, 35, B2TA 19, 35, B2TB 19, 35,
WB2B 19, 26, 35, B2HA 19, 28, 35, B2HB 19, 26, 35)
D
Combustion air opening
a Equivalent vent length (exhaust)