16
5608 741 - 04
Vitodens Rigid and Flex Venting Systems Installation
Side Wall Venting Layouts (Coaxial)
Layout with basic coaxial vent componentry
Standard side wall venting layout
Standard sizes of boiler flue gas adaptors (item
1
)
Boiler model
Adaptor Size
WB1B 26, 35
60 / 100
WB2B 19, 26, 35
60 / 100
WB2B 45, 60
80 / 125
WB2B 80, 105
110 / 150
B2TA 19, 35
60 / 100
B2TB 19, 35
60 / 100
B2HA 19, 28, 35
60 / 100
B2HB 19, 26, 35
60 / 100
B2HA 45, 60
80 / 125
B2HB 45, 57
80 / 125
B2HA 80, 88, 100, 112, 150
110 / 150
1
Vent pipe adaptor
2
Transition adaptor for models 80, 88, 100, 105,
112, 150
M&G Duravent, PolyFlue 110/150 to 100/150
or InnoFlue Centrotherm 110/150 to 110/160
3
Elbow, 87º
4
Straight pipe
5
Vent termination (incl. wall flashings)
Total length of vent termination pipe may be shortened,
if required. Follow manufacturer’s instructions.
6
Protective screen
WARNING
Protective screen MUST be installed.
7
Mounting clip (vent support system)
A
Combustion air intake
B
Flue gas outlet
IMPORTANT
For WB2B 80, 105 and
B2HA 80, 88, 100, 112, 150 models only
Transition 110/150 to 100/150 M&G Duravent
Transition 110/150 to 110/160 Centrotherm
Max. wall thickness
19.6 in. (500 mm)
Side Wall Vent Installation (Coaxial)