Vitodens Rigid and Flex Venting Systems Installation
Vent Length Requirements
(continued)
Vitodens 200-W WB2B 45, 60, 80, 105,
B2HA 45, 60, 80, 88, 100, 112, 150, B2HB 45, 57
Maximum vent/air intake pipe length - vertical
The total equivalent length specified for a two pipe system
is the total
combined
length of the exhaust vent and air
intake pipe system. Do not exceed these maximum lengths.
See table below as well as illustrations above for reference.
All PP(s) vent material and air intake (if PP(s) used) must be
ULC S636 listed, manufactured by M&G / DuraVent.
Legend
A
Support system
B
Exhaust pipe termination with screen
C
Combustion air intake with screen
a Equivalent vent length (exhaust)
b Equivalent vent length (air intake)
Maximum vent/air intake pipe length - horizontal
(continued)
For PP(s) systems, all exhaust vent and air intake piping
and elbows exposed outside, must be UV resistant
polypropylene (supplied by the vent manufacturer).
IMPORTANT
A
B
C
a
b
Side wall
Caulk here
Exterior caulking
Exhaust/Air intake
pipe and fittings
field supplied
Starter adaptor
Parallel adaptor
Boiler adaptor
Air
Flue
Maximum allowable equivalent length - vertical
Boiler Model
System Ø
See note below
Max. combined equivalent vent length
(a+b)*
2
WB1B 26, 35
2 in. (51 mm)
3 in. (76 mm
4 in. (102 mm)*
1
98 ft. (30 m)
164 ft. (50 m)
200 ft. (61 m)
WB2B 19, 26, 35, B2HA 19, 28, 35, B2TA 19, 35
B2HB 19, 26, 35, B2TB 19, 35
2 in. (51 mm)
3 in. (76 mm)*
1
4 in. (102 mm)*
1
115 ft. (35 m)
148 ft. (45 m)
180 ft. (55 m)
WB2B 45, 60, B2HA 45, 60, B2HB 45, 57
3 in. (76 mm)
4 in. (102 mm)*
1
98 ft. (30 m)
148 ft. (45 m)
WB2B 80, 105, B2HA 80, 88, 100, 112
4 in. (102 mm)
131 ft. (40 m)
B2HA 150
4 in. (100 mm)*
3
5 in. (125 mm)*
4
131 ft. (40 m)
131 ft. (40 m)
*
1
2 in. to 3 in. or 2 in. to 4 in. increaser field supplied.
*
2
See illustration above
*
3
Due to higher exhaust vent pipe resistance, there is an automatic input reduction of 9% for model B2HA 150
when a 4 inch diameter vent pipe is used.
*
4
4 in. to 5 in. increaser field supplied.
Direct Venting (Two-pipe System)