45
5608 741 - 04
Vitodens Rigid and Flex Venting Systems Installation
Direct Venting (Two-pipe System)
Vent Length Requirements
(continued)
Maximum vent/air intake pipe length - vertical
(continued)
Note:
For combination of different vent/air intake pipe
diameters, such as Ø 3 in. stainless steel vent with
Ø 2 in. (PP(s), CVPC, PVC, ABS) air intake pipe, the
total equivalent length must be used for the smaller
pipe
diameter.
Minimum vent length is 3.3 ft. (1 m).
Legend
A
Support system
B
Flashings
C
Exhaust (straight coupling) with screen
D
Combustion air intake with screen
All PP(s) vent termination elbows, must be secured in
place as specified by manufacturer.
Vertical Vent Installation:
Vitodens 100-W WB1B 26, 35,
Vitodens 222-F B2TA 19, 35,
Vitodens 222-F B2TB 19, 35,
Vitodens 200-W WB2B 19, 26, 35,
Vitodens 200-W B2HA 19, 28, 35
Vitodens 200-W B2HB 19, 26, 35
Vertical Vent Installation:
Vitodens 200-W WB2B 45, 60, 80, 105,
Vitodens 200-W B2HA 45, 60, 80, 88, 100, 112, 150
Vitodens 200-W B2HB 45, 57
IMPORTANT
For PP(s) systems, all exhaust vent and air intake piping
and elbows exposed outside, must be UV resistant
polypropylene (supplied by the vent manufacturer).
IMPORTANT
Vent system
a (min. distance) *
60/100
25 in. (635 mm)
80/125
25 in. (635 mm)
100/150
110/160
30 in. (762 mm)
1 ft. (0.3 m)
*(See vent manufacturer’s specifications).
Legend
a Equivalent length (exhaust)
b Equivalent length (air intake)
c min. 18 in. / max. 48 in.
d min. 12 in.
e min. 12 in.
f 6 in. over max. local snow level (check with your local
weather office for details)