54
Terminals
Function
Explanation
X3.1
Switched phase.
Via control unit ON/OFF switch.
Note
Observe the total load (1000 W) of all con-
nected components.
X3.3
X3.4
Flow limiter
Requires zero volt
N/O
contact:
■ Closed: Heat pump in operation
■ Open: Heat pump shut down
■ Breaking capacity 230 V, 015 A
Remove jumper when making this connec-
tion.
X3.6
X3.7
G
Power-OFF (factory-fitted
jumper).
Requires zero volt
N/C
contact:
■ Closed: Heat pump in operation
■ Open: Heat pump shut down
■ Breaking capacity 230 V, 0.15 A
Remove jumper when making this connec-
tion.
Note
■ No parameters need to be set.
■ The compressor is "forced" off as soon
as the contact opens.
■ The supply voltage to the respective
components is switched off by the pow-
er-OFF contact signal.
■ For the instantaneous heating water
heater, the stages to be switched off can
be selected (parameter "Output for in-
stant. heating water heater at power-
OFF 790A").
■ For further information regarding power-
OFF, see chapter "Power supply".
Installation sequence
Electrical connection
(cont.)