36
Danger
Damaged cable insulation can cause injury and
damage to the appliance.
Route cables so they cannot touch very hot,
vibrating or sharp-edged components.
Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
age.
■
Route LV leads < 50 V and
>
50 V/230 V~/400 V~ cables separately.
■
Only strip the minimum of insulation from
cables as close as possible to the terminals
and bundle tightly to the corresponding termi-
nals.
■
Secure cables with cable ties/strain relief fit-
tings.
This ensures that, should there be a fault, for
example when detaching a wire, the wires can-
not drift into the adjacent voltage area.
When routing on-site power cables, observe the loca-
tion of the cable entries into the appliance through the
back panel (see page 14 to page 16).
400 V~
230 V~
<50 V
Fig.30
1.
Route LV leads through "< 50 V" entry to heat pump
wiring chamber.
2.
Route 230 V cables through "230 V" entry to heat
pump wiring chamber.
Secure 230 V cables with cable ties.
Note
Route LV leads and 230 V/400 V cables as far
apart as possible.
3.
Route power cable for compressor through "400 V"
entry to the heat pump wiring chamber.
Always
secure the power cable with strain relief fit-
tings.
Note
Additional strain relief fittings are required on site,
as the wall clearance is ≥ 80 mm.
For power supply, see from page 48.
Installation sequence
Making the electrical connection
5549 984 GB
Installation
Summary of Contents for KWT BW 301.B090
Page 99: ...99 5549 984 GB...