62
Ice store/solar air absorber
Parameters for ice store and solar air absorber
Setting
"System definition"
Ó
"Select primary source 7030"
"1"
"System definition"
Ó
"External extension 7010"
"2"
"Solar"
Ó
"Type solar control unit 7A00"
"2"
"System definition"
Ó
■
"Start hysteresis solar air absorber 7031"
"0"
to
"500"
(
≙
0 to 50 K)
■
"Min. runtime to suppress summer mode 7035"
"0"
to
"1440"
min
■
"Last calendar week for summer mode 7036"
Calendar week
"1"
to
"53"
Energy meter
Electricity meter parameters
Setting
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"1"
"Photovoltaics"
Ó
"Threshold for electrical power 7E04"
"0"
to
"300"
(
≙
0 to 30 kW)
Extended menu:
"PV ctrl strategy"
or
"Photovoltaics"
Ó
Enable required functions for on-site power
consumption.
■
"Enable own energy consumptn for set DHW temperature 2
7E10"
"1"
■
"Enable own energy consumption for DHW heating 7E11"
"1"
■
"Enable own energy consumptn for heating water buffer cyl.
7E12"
"1"
■
"Enable own energy consumption for heating 7E13"
"1"
Extended menu:
"PV ctrl strategy"
or
"Photovoltaics"
Ó
Specify the temperature differential to the
selected set value for the chosen function.
■
"Raise set DHW cylinder temperature PV 7E21"
"0"
to
"200"
(
≙
0 to 20 °C)
■
"Raise set heating water buffer cylinder temp PV 7E22"
"0"
to
"100"
(
≙
0 to 10 °C)
■
"Raise set room temperature PV 7E23"
"0"
to
"50"
(
≙
0 to 5 °C)
Ventilation
Ventilation unit parameters
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Other enabling settings, if applicable:
"Ventilation"
Ó
■
"Enable preheater bank electric 7D01"
"1"
■
"Enable reheater bank hydraulic 7D02"
"1"
■
"Enable humidity sensor 7D05"
"1"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 984 GB