60
Pump/component
Parameter
Setting
Vitocom 100, type GSM
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension
"System definition"
Ó
"External extension 7010"
"1"
External EA1 extension
"2"
External AM1 extension
"3"
EA1 and AM1
Note
For external function parameters see
"External functions" table.
2-stage heat pump
Parameter
Setting
Compressor 2:
■
"Enable compressor 5100"
"1"
■
"Output compressor stage 2 5130"
Value corresponding to the rated heating
output of heat pump stage 2, see type plate
External functions
External functions
Parameter
Setting
External demand
"Internal hydraulics"
, if applicable
Ó
"Flow temperature for external de-
mand 730C"
Set flow temperature for ex-
ternal demand
External starting of the compressor;
mixer in control mode or OPEN
"System definition"
Ó
"Effect of external demand on heat
pump/heating circuits 7014"
"0"
to
"7"
(Observe parameter
"Flow
temperature for external de-
mand 730C"
)
External changeover of the operating
status of various system components
"System definition"
Ó
"System components for external
changeover 7011"
"0"
to
"127"
"System definition"
Ó
"Operating status for external
changeover 7012"
"0"
to
"3"
"System definition"
Ó
"Duration of external changeover
7013"
"0"
to
"12"
External blocking of compressor and
pumps
"System definition"
Ó
"Effect of external blocking on
pumps/compressor 701A"
"0"
to
"31"
External blocking of the compressor;
mixer in control mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on heat
pump/heating circuits 7015"
"0"
to
"8"
"System definition"
Ó
"Effect of external blocking on
pumps/compressor 701A"
"0"
to
"31"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 984 GB