Observe engineering information.
Heat pump technical guide
Commissioning the system
Commissioning (configuration, parameter settings and
function checks) can be carried out with or without the
commissioning wizard (see following chapter and serv-
ice instructions for the "Vitotronic 200 heat pump con-
trol unit").
Note
The type and extent of the parameters depend on the
heat pump type, on the selected system scheme and
the accessories employed.
Commissioning with commissioning wizard
The commissioning wizard automatically guides you
through all the menus where settings have to be made.
For this, "Coding level 1" is automatically active.
!
Please note
Incorrect operation at "Coding level 1" may
result in damage to the appliance and the heat-
ing system.
Observe the service instructions for the
"Vitotronic 200 heat pump control unit", other-
wise the appliance warranty will be void.
Switch on the ON/OFF switch on the heat pump con-
trol unit.
■
The prompt
"Commissioning Start?"
appears
automatically
on 1st commissioning.
Note
The commissioning wizard can also be started
man-
ually
:
To do this, press and hold
when switching on the
heat pump control unit (progress bar visible).
■
When the appliance is first commissioned, the dis-
play is in German:
Sprache
Dansk
Cesky
Bulgarski
Deutsch
Wählen mit
ê
ê
ç
DE
BG
CZ
DK
ê
ê
(
Fig.38
■
Manually switching some appliance components dur-
ing commissioning enables the heat pump control
unit to display messages. These are not appliance
faults.
Commissioning, inspection, maintenance
Checking expansion vessels and the primary circuit/heating circuit pres-
sure
5549 984 GB