12
Minimum clearances
A
B
C D
E
600
600
Fig.3
E
B
A
C D
600
600
600
C D
Fig.4
A
Clearance subject to on-site installation and loca-
tion
B
Clearance for installation and service (e.g. for
removing and cleaning the tubular heat exchang-
ers)
■
Type BW:
≥
500 mm
■
Type WW:
≥
2000 mm
C
Cable entries:
On-site strain relief clamps required (wall clear-
ance ≥ 80 mm).
D
■
When using hydraulic connection accessories
(connection set and Victaulic flange adaptor set,
2
½"
or 3
"
version):
≥
1000 mm
■
On-site hydraulic connections:
≥
600 mm
E
■
Without anti-vibration parts (side sections):
≥
855 mm
Note
When installing cascades (2 to 5 heat pumps), observe
the respective minimum clearances in accordance with
the preceding graphics.
Sound attenuating plinth
Position the heat pump on a base prepared on site for
the purpose of noise attenuation and even weight dis-
tribution.
Note
For corner installation, enlarge the base by the mini-
mum clearances (see chapter "Minimum clearances").
Preparing for installation
Siting
(cont.)
5549 984 GB
Installation