58
Start
function check
Select
function
Carry out
subscriber check
Carry out
actuator test
Display
signal inputs
Display
sensor values
Set
parameter
Start commissioning?
Select
parameter group
Set
language
Set
date/time
Temperature sensors
Signal inputs
Actuator test
Commissioning terminated
Control mode
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
NO
YES
OK
Functional
check
Coding
level 1
Subscriber check (LON)
Set
time
Set
date
Fig.39
Commissioning without the commissioning wizard
Activating the service menu
The service menu can be activated from any other
menu.
Hold down
OK
+
å
simultaneously for approx. 4 s.
Disabling the service menu
The service menu remains active until it is ended with
"Terminate service?"
, alternatively it ends if no oper-
ation takes place for 30 min.
Setting parameters using the "System scheme"
example
To set a parameter, first select the parameter group
and then the parameters.
All parameters are displayed as plain text. A parameter
code is also assigned to each parameter.
Service menu:
1. Hold down
OK
+
å
simultaneously for approx.
4 s.
2. Select
"Coding level 1"
.
3. Select parameter group:
"System definition"
4. Select parameter:
"System scheme 7000"
5. Set system scheme:
"6"
Alternatively, if the service menu was already active:
Extended menu
1.
å
2.
"Service"
3. Select
"Coding level 1"
.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 984 GB