Extinguishing water container
Part no. 7387 785
< 500
A
B
C
D
A
N25 fill level monitoring
B
Extinguishing water container 25 l
C
Material supply
D
Combustion
Note
Part of the boiler.
Note
■ Adjustment, valve, Danfos AVTA 15 50–90 °C
3 corresponds to 80 C°.
■ Lines should be secured in metal pipes (½“).
■ The cold water supply must not be able to be isolated without the aid
of a tool.
Extinguishing facility with cold water supply
Part no. 7388 521
KW
B
A
KW
B
A
A
Combustion
B
Dosing container with separating barrier
KW Cold water supply DN 15 ½“ min. 2.0 bar, max. 3.0 bar
Note
■ Lines should be secured in metal pipes (½“).
■ The cold water supply must not be able to be isolated without the aid
of a tool.
Note
Alternative or additional safety equipment. A shut-off gate valve is
required as standard for an unpressurised material store or a rotary
lock valve for a material store with overpressure or underpressure
(charging with fan, e.g. wood processing operations).
Back burning protection, boiler system
The boiler system back burning protection is part of the standard deliv-
ery.
Design information
(cont.)
40
PYROTEC
6
5822 511 GB