2.2 Specification
Specification
Trade name
PYROTEC grate combustion
Rated output
390
530
720
950
1250
Part no.:
7423 674
7423 675
7423 676
7423 677
7423 678
Output data
Rated output
kW
390
530
720
950
1250
Continuous output
*1
kW
390
530
720
950
1250
Minimum output Q
min
*2
kW
97
132
180
238
312
Output with woodchips W 45
*3
kW
380
515
700
920
1210
Heating data
Content on hot gas side
l
1540
2280
2830
4050
5210
Permissible shutdown temperature of the high
limit safety cut-out
°C
100
100
100
100
100
Minimum return temperature
°C
65
65
65
65
65
Grate ash container capacity
l
240
240
240
240
240
Ash container capacity, flue gas dust extractor
l
240
240
240
240
240
Boiler water content
l
1150
1444
1861
1943
2482
Water-side pressure drop (diff. 15 K)
mbar
13
23
43
26
45
Permiss. operating pressure
Test pressure
bar
7.8
7.8
7.8
7.8
7.8
Maximum operating pressure
bar
6
6
6
6
6
Heating surface
m
2
26.32
42.50
55.50
74.80
91.00
CE designation
CE
CE
CE
CE
CE
Boiler class to DIN EN 303-5
3
3
3
3
3
Overall dimensions
Total length
mm
4370
4870
5257
5447
5992
Total width (boiler)
mm
1274
1247
1380
1612
1612
Total width (boiler with supply screw conveyor) mm
2382
2382
2488
2852
2852
Total height (boiler)
mm
2378
2536
2834
3035
3230
Total height (boiler with induced draught fan)
mm
3186
3186
3378
3452
3717
Weight
Boiler
kg
1680
2707
3291
4874
5563
Combustion block
kg
2970
4238
4953
5779
6520
Displacer rods
kg
394
394
394
538
538
Flue gas fan
kg
60
62
78
82
107
Supply screw conveyor
kg
153
153
153
190
190
Total dry weight
kg
5230
7554
8869
11463
12919
Total wet weight
kg
6380
8998
10730
13406
15400
Max. power consumption
Ignition unit
W
1600
1600
1600
1600
1600
Electrical connections (total)
W
5410
7020
8120
9350
11150
During heating operation
W
2880
3570
4560
5170
6790
Supply screw conveyor
W
1100
1500
1500
2200
2200
Primary air fan 1
W
140
300
300
480
480
Primary air fan 2
W
900
900
900
900
900
Secondary air fan
W
900
1500
1500
1850
1850
Flue gas fan
W
1100
1100
2200
2200
4000
Grate drive
W
120
120
120
120
120
Electrical power consumption with Q
N
W
2880
3570
4560
5170
6790
Electrical power consumption with Q
min
W
2340
2900
3710
4150
5470
Boiler connections
Boiler flow and return
DN
100
100
100
125
125
Extinguishing water connection
R
¾
¾
¾
¾
¾
Boiler drain and fill valve
R
1½
1½
1½
1½
1½
Safety heat exchanger
R
4 x ½
4 x ½
8 x½
8 x ½
8 x ½
Sensor well for TS
R
½
½
2 x ½
2 x ½
2 x ½
*1
Levelled output as base load boiler in continuous operation with pneumatic cleaning
*2
Q
≥
Q
min
: Output operation modulating control (variable output control)
Q
≤
Q
min
: Low load with ON Q
min
/ OFF (Stop and Go operation)
*3
Wet fuels: > W45 further limitation-related output, efficiency and control characteristics
PYROTEC
(cont.)
8
PYROTEC
2
5822 511 GB