Hatched surface
Floor in heat-resistant version
Surface medium grey Boiler supporting surface
Foundation properties
Trade name
PYROTEC grate combustion
Rated output
kW
390
530
720
950
1250
Part no:
7423 674
7423 675
7423 767
7423 677
7423 678
a
mm
1026
1026
1112
1360
1360
b
mm
1826
1826
1912
2160
2160
c
mm
4221
4721
4912
5096
5641
d
mm
1260
1260
1400
1630
1630
e
mm
2561
3061
3112
3066
3611
Requirements of Sample Combustion Order
The installation room must meet the standards laid down by the "Fire
Regulations" of the respective country. Observe the Building Regula-
tions and Fire Regulations of the respective country of installation.
Emergency stop switch
The burner, the fuel supply equipment and the burner control units
must be able to be switched OFF at any time by an emergency stop
switch installed outside the installation room.
Provide a sign adjacent to the emergency stop switch with the inscrip-
tion "EMERGENCY STOP SWITCH - COMBUSTION".
Combustion air supply
For open flue combustion equipment with a total rated output in excess
of 35 kW, the fresh ventilation is deemed to have been verified if the
combustion equipment is located in areas which provide an aperture
or duct leading outdoors.
At 35 kW rated output, the cross-section of the aperture must be at
least 150 cm
2
. For every kilowatt rated output in excess of 35 kW, the
aperture must be 2 cm
2
larger than stated above.
Pipes must be sized to provide equivalent flow rates. The required
cross-section may be split over a maximum of 2 apertures or pipes.
A
A = 150 cm² + 2 kW
cm² x (Σ
²
n – 35 kW)
Σ
²
n
= total of all rated outputs in kW
Design information
(cont.)
PYROTEC
35
5822 511 GB
6