Trade name
PYROTEC grate combustion
Rated output
390
530
720
950
1250
Part no.:
7423 674
7423 675
7423 676
7423 677
7423 678
Flue gas
*4
Average temperature (gross
*5
)
Mean flue gas temperature with Q
N
*6
°C
160
160
160
160
160
Mean flue gas temperature with Q
min
°C
120
120
120
120
120
Mass flow rate
Q
N
; W5; O
2
8 %
g/s
219
297
404
532
700
Q
W35
; W45; O
2
10 %
g/s
303
412
560
736
968
Flow rate
Q
N
; W5; O
2
8 %; 150 °C
m
3
/s
0.26
0.36
0.48
0.63
0.83
Q
W35
; W45; O
2
10 %; 150 °C
m
3
/s
0.37
0.50
0.67
0.88
1.15
CO
2
content in the flue gas
%
14.7
14.7
14.7
14.7
14.7
Flue outlet
7
mm
350
350
350
400
450
Required draught
(at full load)
Pa
0
0
0
0
0
Efficiency
At full load
*7
%
91
91
91
91
91
At partial load
%
90
90
90
90
90
*4
Values for calculating the size of the flue system to DIN EN 13384, based on 12.0% CO
2
.
*5
Actual flue gas temperature as average gross value as per EN 304 at 20 °C combustion air temperature.
*6
Flue gas temperature: Reduction possible by inserting displacer rods (Q
N
-20 °C; Q
min
- 10 °C).
*7
For dry fuels (W5-W20) without recirculation, lower.