6.22 Sound insulation
Braces
To avoid the transmission of structure-borne noise during the opera-
tion of the fuel transportation equipment, the braces and the anchors
of the relevant conveyor device are placed on high quality Sylomer
bases (plastic anti-vibration mounts for noise attenuation) or anchored
with a Sylomer support and a fixing plate in the building structure. The
anchors with heavy load anchors are separated from the braces with
Sylomer washers.
Standard delivery:
■ Sylomer washer
■ Sylomer support
■ Sylomer base
■ Fixing plate for the braces of the relevant equipment
Trade name
Sound insulation, braces
Type
Discharge
conveyor
Screw
conveyor
Supply
Spring core
discharge
Horizontal
discharge
Removal of
ash
Flue gas
dust extractor
Part no:
7419 991
7419 992
7419 995
7419 996
7419 997
7419 998
7419 999
Note
■ Depending on the means of fuel transportation, the sound insulation
article should be used once, e.g. 1 AH + 1 sound insulation AH-AS
■ Installation room characteristics relating to the physical building
structure largely determine the transmission of structure-borne noise
in the building. It is important to note that the specified measures do
not offer full sound insulation.
■ Building related measures (brick openings, fire barriers, floating
screeds, etc.) must be coordinated with structural engineers and
architects and are not part of standard delivery and therefore not
within our area of responsibility.
Appendix
7.1 Sizing the expansion vessel
In accordance with EN 12828, water heating systems must be equip-
ped with a diaphragm expansion vessel. The size of the expansion
vessel is subject to the heating system specification and should be
checked in each case.
Quick selection table for calculating the vessel size V
n
Safety valve
p
sv
bar
3.0
V
n
Pre-charge
pressure
bar
1.0
1.5
1.8
litres
System vol-
ume V
A
litres
220
—
—
25
340
200
—
35
510
320
200
50
840
440
260
80
1050
540
330
100
1470
760
460
140
2100
1090
660
200
2630
1360
820
250
3150
1630
990
300
4200
2180
1320
400
5250
2720
1650
500
Selection example
Datum:
p
sv
= 3 bar (response pressure of the safety valve)
H
= 13 m (static ceiling of the system)
Q
= 18 kW (rated output of the heat source)
v
= 8.5 l/kW (specific water capacity)
panel radiators 90/70 °C
V
PH
= 1000 l (volume of buffer cylinder)
The specific water capacity v was determined as follows:
■ Radiators: 13.5 l/kW
■ Panel radiators: 8.5 l/kW
■ Underfloor heating: 20 l/kW
Calculation:
V
A
= Q x v + 1000
V
A
= 18 kW x 8.5 l/kW + 1000 l
= 1153 l
If possible, when calculating the gas pre-charge pressure, select a
supplement of 0.2 bar:
p
0
≥
H/10 + 0.2 bar
p
0
≥
(13/10 + 0.2 bar) = 1.5 bar
From the table:
With p
sv
= 3 bar, p
0
= 1.5 bar, V
A
= 1153 l
V
n
= 250 l (for V
A
max. 1360 l)
Design information
(cont.)
82
PYROTEC
7
5822 511 GB
Summary of Contents for KOB PYROTEC