5726 783
PYROMAT DYN45 - DYN85 Issue 1.0
Page 47 of 72
Screen
number
Parameters
Factory setting
04
Heating period 1, start:
Set switch-over time from reduced temperature
or off to normal temperature.
L
This setting is only available with day / night
or day / off operating modes.
06:00
05
Heating period 1, end:
Set switch-over time from normal temperature to
reduced temperature (or off).
L
This setting is only available with day / night
or day / off operating modes.
22:00
06 – 23
Heating periods 2-7:
Dependant on the number of heating periods
(figure number 2), comprising heating days,
start and end.
-
24
Flow temperature at +5°C outside temperature. 43°C
25
Flow temperature at -15°C outside temperature 64°C
26 Temperature
room
day:
Target room temperature in day operation.
20°C
27 Temperature
room
night:
Target room temperature in night operation.
15°C
28
Night flow temperature drop of:
The temperature set is subtracted from the
calculated flow temperature when night drop-
down is operating.
-6°C
29
Flow temperature, maximum:
Maximum limit for flow temperature.
70°C
30 ECO
mode:
The heating is switched on and off depending
on requirement by the ECO economy-controller.
Yes
31
Switch-off under system temperature:
Should the room unit group be switched off
when the system temperature drops below a
minimum?
No
32
Frost protection function:
With the frost protection function switched on
the room unit will be switched on if there is a
danger of frost.
Yes
33
Excess heat take-off:
If there is a danger of the PYROMAT DYN
overheating, e.g. through too much fuel being
fed in by hand, then the excess heat can be
taken off if desired.
The room unit is controlled under "Maximum
flow temperature".
No