PYROMAT DYN45 - DYN85 Issue 1.0
Page 35 of 72
5.7.2 Heat-up in log operation
Ensure that the following preconditions are met:
Operating pressure in the heating system is checked.
The heating system is ventilated.
Customer's on-site slide valves for heating feed and return are open.
Ventilation apertures are open.
All doors and covers are closed.
Burner group ball valves are open.
Turbolators are removed from the pipe heat exchanger.
If de-ashing (optional) is available:
Remove cover over the auger in the combustion chamber (Fig. 8).
If de-ashing (optional) is not available:
Insert cover over the auger in the combustion chamber (Fig. 9).
Fig. 8
De-ashing (optional) available:
Remove cover.
Fig. 9
De-ashing (optional) not
available: Insert cover in
recess.
Danger of deflagration!
Serious injuries through highly inflammable materials when igniting the fuel.
Warning!
1. Use only paper, cardboard and firewood to light the fuel.
2. Under no circumstances use highly inflammable materials such as petrol, oil or
solvents to light the fuel.
1. Open the ash pan door and light the paper, ideally along the whole width of the
firebox.
L
The fire can spread very quickly over the whole grate surface.
Rapid heating up of the combustion chamber quickly provides a perfect
combustion.
2. Press F1 "PYROMAT manual" button on the controller.
3. Leave the ash pan door approx. 10cm open.
4. Monitor the heating system during the pre-heating process until an exhaust gas
temperature of approx. 110°C is indicated.
5. If an exhaust gas temperature of approx. 110°C is indicated:
Close the ash pan door completely.
L
For optimal and fault-free heating operation ensure that all covers and doors are
closed tightly during the combustion.
L
The pre-heating process is completed.