PYROMAT DYN45 - DYN85 Issue 1.0
Page 33 of 72
5.7 Log operation
L
Before log operation ensure that the amount of heat generated can be taken off and
stored by the heating system.
If the amount of heat can not be taken off then this will result in an overheating of
the boiler and the temperature limiting safety switch will be activated.
The boiler will be supplied with cold mains water via the safety heat exchanger and
cooled.
The combustion time is dependant on the type of wood used:
Deciduous wood filling:
approx. 4 hrs
Coniferous wood willing: approx. 3 hrs
5.7.1 Fill
wood
L
With heating systems with storage as hydraulic switcher:
Only reduced heating operation possible, only fill firebox partially - depending on
heat take-off, max 20 to 40kg per filling.
L
With heating systems with ECO function (optional), storage with storage control
valve:
Unrestricted heating operation possible - only fill in so much wood as the storage
can take energy from, until the maximum storage temperature of 90°C is reached.
Heating system is
out of operation
1. Open firebox door.
2. If the grate slots are covered in fine ash:
Remove the ash until the grate is covered with a maximum 2cm of charcoal.
3. If there are still residual embers on the grate:
Let the embers go out, do not feed in fuel.
Danger of deflagration!
Low temperature gas forming as a result of sawdust or chopped wood pieces during the
heat-up process.
Caution!
1. Under no circumstances feed sawdust or chopped wood pieces directly onto the grate.
4. Spread paper and good combustible wood across the complete width of the boiler
approx. 25cm high, so that a good air-permeable bed exists.
5. Arrange split logs or wood pieces horizontally and compactly over the complete
width of the boiler in the firebox.
6. Remove any dirt that may exist on the contact surfaces of the firebox door.
7. Close firebox door.