PYROMAT DYN45 - DYN85 Issue 1.0
5726 783
5.4 F4 key "PYROMAT loading"
It may be necessary to alter the settings:
when the fuel is changed
when the heating system is adapted and optimised
L
Alterations must only be carried out in conjunction with your installation specialists.
Adjustable parameters
Screen
number
Parameters
Factory setting
01 Cleaning:
Activating the cleaning function. De-ashing is in
continuous operation, exhaust blower running at
maximum speed.
No
02
Grate drive pause time:
Clock circuit de-ashing module (optional) and
agitator. The pause time is adjustable. An
impulse always causes a complete revolution of
the agitator.
400s
03
Dosing container, time to empty:
If the runtime set for the feed auger (with free
feed auger light barrier) has expired, the
material supply starts.
5s
04
Feed system 1, delay time:
Set switch-on delay for feed system 1 (e.g.
rotary valve, feed auger, ... ).
3s
06 to 33
Feed systems 2 to 15:
Adjust switch-on and switch-off delay for feed
systems 2 to 15.
-
34
Extraction system 1, delay time:
Set switch-on delay for extraction system 1 (e.g.
spring core extractor, ascending extractor,... ).
3s
35
Extraction system 1, pulse time:
Set clock circuit pulse time for extraction system
1 (e.g. spring core extractor, ascending
extractor,... ).
5s
36
Pause in extraction system 1:
Set clock circuit pause time for extraction
system 1 (e.g. spring core extractor, ascending
extractor,... ).
0s
37
Extraction system 2, delay:
Set switch-on delay for extraction system 2 (e.g.
spring core extractor, ascending extractor,... ).
3s
38
Extraction system 2, pulse time:
Set clock circuit pulse time for extraction system
2 (e.g. spring core extractor, ascending
extractor,... ).
5s