5726 783
PYROMAT DYN45 - DYN85 Issue 1.0
Page 65 of 72
No. Error report display
Error sensor
Possible cause
Check, rectification
20 Water
level
in
extinguishing water
container
Function key F3
illuminates red.
Level float switch in
extinguishing water container
Too little water in extinguishing
water container.
1. Fill the extinguishing water container with
water.
2. Cancel error with OK.
25
Light barrier - ember
monitoring system
Function key F3
illuminates red.
Light barrier for ember
monitoring system
Sight glasses dirty, ash build-up in
the apertures.
Defective error sensor.
1. Remove and clean sight glasses on both
sides. Remove dirt and ash deposits from the
apertures.
2. Cancel error with OK.
26
Light barrier - feed
auger
Function key F3
illuminates red.
Light barrier in feed auger
dosing container
Light barrier dirty.
Blockage in the dosing container.
1. Clean light barrier.
2. Clear blockage in the dosing container.
3. Cancel error with OK.
96
Feed auger pipe too hot
Temperature sensor on the feed
auger
Power
failure.
Resultant faults caused by over-
temperature.
Ember monitoring system light
barriers dirty.
1. Contact an electrician.
2. Check light barriers at ember bed.
3. Cancel error with OK.
81
to
93
BUS fault, no
connection to. . .
Function key F3
illuminates red.
Data transmission line, bus
connection
Bus connection interrupted.
1. Check the connectors.
2. Defective data transmission line? Have data
transmission line replaced.
3. Call
suppliers.