Page 42 of 72
PYROMAT DYN45 - DYN85 Issue 1.0
5726 783
6.2 Utility
water heater
Function ECO-B1
If the utility water temperature drops then this is re-heated by the boiler or the heat
storage via the integrated heat exchanger. An appropriate temperature differential
(selectable between differential temperature or fixed preset temperature) is a
prerequisite.
The heating times (day and week program) can be adjusted via the integrated timer.
Function ECO-B2
If the utility water temperature drops then this is re-heated by the boiler or the heat
storage via the integrated heat exchanger. An appropriate temperature differential
(selectable between differential temperature or fixed preset temperature) is a
prerequisite.
The hot water flow rate is controlled by the return temperature (flow control). This
results in an optimised storage stratification with a higher temperature maintained in the
storage feed over a longer period.
The heating times (day and week program) can be adjusted via the integrated timer.
Adjustable parameters
Screen
number
Parameters
Factory setting
01 Operating
mode:
Operating mode selection.
Off
Utility water heating is switched off.
Timer
The utility water heating is controlled in
accordance with a timer program. The boiler
is only heated up during the heating time.
On
The boiler is heated up when there is a
demand for heat and when the system
temperature is sufficient.
Manual
The pump is switched on, the valve is not
controlled.
L
Use this setting only for emergency
operation if a fault message is shown on the
display.
1. Inform your heating specialists for further
instructions on fault rectification.
Timer
02
Number of heating periods:
The week program is entered in the form of
heating periods. Each week program comprises
heating days, start and end.
There are a maximum of 7 heating periods
available.
1