70
Coding in the delivered condition
Possible change
Pump control in "Only DHW"
F6:25
In the "Only DHW" oper-
ating mode, the internal
circulation pump is per-
manently ON (only for
constant temperature
control units)
F6:0
In the "Only DHW" operat-
ing mode, the internal cir-
culation pump is perma-
nently OFF
F6:1
to
F6:24
In the "DHW only" operat-
ing mode, the internal cir-
culation pump will be star-
ted for 10 min respectively
1 to 24 times per day.
Pump control in "Standby mode"
F7:25
In "Standby mode", the
internal circulation pump
is permanently ON (only
for constant temperature
control units)
F7:0
In "Standby mode", the
internal circulation pump is
permanently OFF
F7:1
to
F7:24
In "Standby mode", the
internal circulation pump in
operating mode will be
started for 10 min respec-
tively 1 to 24 times per
day.
Start temperature raising
F8:-5
Temperature limit for ter-
minating the reduced
mode -5 ºC, see example
on page 141.
Observe the setting of
coding address "A3" (only
for weather-compensa-
ted control units)
F8:+10
to
F8:-60
Temperature limit adjusta-
ble from
+10 to -60 °C
F8:-61
Function disabled
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temp. -14 ºC, see exam-
ple on page 141 (only for
weather-compensated
control units)
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5457 552 GB