100
Display
Explanation
Start valve Heating
Diverter valve set to heating mode
Start valve centre
Diverter valve in central position (filling/draining)
Start valve cylinder
Diverter valve set to DHW mode
Start htg circ pump HC2
Heating circuit pump output enabled (extension to heat-
ing circuit with mixer)
Open mixer HC2
"Mixer open" output enabled (extension to heating circuit
with mixer)
Close mixer HC2
"Mixer closed" output enabled (extension to heating cir-
cuit with mixer)
Start htg circ pump HC3
Heating circuit pump output enabled (extension to heat-
ing circuit with mixer)
Open mixer HC3
"Mixer open" output enabled (extension to heating circuit
with mixer)
Close mixer HC3
"Mixer closed" output enabled (extension to heating cir-
cuit with mixer)
Start outp. int. exten. H1
Output at internal extension enabled
Start AM1 output 1
Output A1 at extension AM1 enabled
Start AM1 output 2
Output A2 at extension AM1 enabled
Start EA1 output 1
Contacts P - S at plug
aBJ
for extension EA1 closed
Constant temperature control unit
1.
Press
OK
and
å
simultaneously
for approx. 4 s.
"
Ü
" flashes on the display.
2.
Select
Ú
" " and confirm with
OK
.
3.
Select required actuator (output) with
V
/
v
(see following table):
4.
Confirm selected actuator with
OK
.
The display shows the number for the
activated actuator and "
ON
".
The following actuators (relay outputs) can be controlled subject to system
design:
Display
Explanation
1
Burner operates at minimum output; internal pump starts
2
Burner operates at maximum output; internal pump starts
3
Internal output
sÖ
(internal pump) is enabled
4
Diverter valve set to heating mode
5
Diverter valve in central position (filling/draining)
6
Diverter valve set to DHW mode
10
Internal extension output enabled
Diagnosis and service scans
Checking outputs (relay test)
(cont.)
5457 552 GB