Function assignment
Select the function of output
aBJ
via
code 36 at the boiler control unit.
Control functions
External heating program changeover
The "External heating program change-
over" function is connected via extension
EA1. There are 3 inputs available at
extension EA1 (DE1 to DE3).
The function is selected via the following
codes:
Heating program changeover
Code
Input DE1
3A:1
Input DE2
3b:1
Input DE3
3C:1
Assign the heating program changeover
function for the respective heating circuit
via code d8 at the boiler control unit:
Heating program changeover
Code
Changeover via input DE1
d8:1
Changeover via input DE2
d8:2
Changeover via input DE3
d8:3
You can select which direction the heat-
ing program changeover takes in coding
address "d5":
Heating program changeover
Code
Changeover towards "Permanently reduced" or "Permanent
standby" mode (subject to the selected set value)
d5:0
Changeover towards "Constant heating mode"
d5:1
The duration of the heating program
changeover can be adjusted in coding
address "F2":
Function description
External extensions (accessories)
(cont.)
5457 552 GB