Coding in the delivered condition
Possible change
Pump idle time, transition red. mode
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value
changes through a
change in operating
mode or through a
change in the set room
temperature (only for
weather-compensated
control units)
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time;
adjustable from 1 to 15
Weather-compensated/room temperature hook-up
b0:0
With remote control:
Heating mode/reduced
mode: Weather-compen-
sated (only for weather-
compensated control
units; change the code
only for the heating circuit
with mixer)
b0:1
Heating mode: Weather-
compensated
Reduced mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
Summer eco function room temperature
b5:0
With remote control: No
room temperature-
dependent heating circuit
pump logic function (only
for weather-compensa-
ted control units; change
the code only for the heat-
ing circuit with mixer)
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table:
Parameter
address b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5457 552 GB