73
7. If you want to reset all codes to
their delivered condition:
Select
Ú
"
7
"
and confirm with
OK
.
When " " flashes, confirm with
OK
.
Note
This also resets codes from coding
level 1.
General/Group "1"
Select
"General"
for weather-compensated control units (see page 72).
Select
"1"
for constant temperature control units (see page 72).
Coding
Coding in the delivered condition
Possible change
00:2
System version 1:
One heating circuit with-
out mixer (A1), with DHW
heating
00:2
to
00:10
For system schemes, see
the following table:
Value
address
00: ...
System
version
Description
2
1
One heating circuit without mixer (heating circuit 1), with DHW
heating (code is adjusted automatically)
4
2
One heating circuit with mixer (heating circuit 2), with DHW
heating
6
3, 4
One heating circuit without mixer (heating circuit 1) and one
heating circuit with mixer (heating circuit 2), with DHW heating
(code is adjusted automatically)
8
5
One heating circuit with mixer (heating circuit 2) and one
heating circuit with mixer (heating circuit 3), with DHW heat-
ing
10
5
One heating circuit without mixer (heating circuit 1), one heat-
ing circuit with mixer (heating circuit 2) and one heating circuit
with mixer (heating circuit 3), with DHW heating (code is
adjusted automatically)
Code 2
Calling up coding level 2
(cont.)
5457 552 GB
Service