95
Fault code dis-
played
System characteristics
Cause
Measures
78
No heating operation and no
DHW heating
Short circuit, process cir-
cuit flow temperature sen-
sor
Replace sorber outlet temperature
sensor, plus process circuit flow
and return temperature sensors.
Start sensor calibration manually
(code "16:1" in the
"Process"
group).
79
No heating operation and no
DHW heating
Lead break, process cir-
cuit flow temperature sen-
sor
Replace sorber outlet temperature
sensor, plus process circuit flow
and return temperature sensors.
Start sensor calibration manually
(code "16:1" in the
"Process"
group).
7A
No heating operation and no
DHW heating
Short circuit, process cir-
cuit return temperature
sensor
Replace sorber outlet temperature
sensor, plus process circuit flow
and return temperature sensors.
Start sensor calibration manually
(code "16:1" in the
"Process"
group).
7B
No heating operation and no
DHW heating
Lead break, process cir-
cuit return temperature
sensor
Replace sorber outlet temperature
sensor, plus process circuit flow
and return temperature sensors.
Start sensor calibration manually
(code "16:1" in the
"Process"
group).
90
Control mode
Short circuit, temperature
sensor
/
Check sensor
/
on solar control
module.
91
Control mode
Short circuit, temperature
sensor
aÖ
Check sensor
aÖ
on solar control
module.
92
No solar DHW heating and, if
natural heat source is solar
thermal, no sorption opera-
tion
Short circuit, collector
temperature sensor
Check temperature sensor
&
on
the solar control module or temper-
ature sensor on the Vitosolic.
93
Control mode
Short circuit, cylinder tem-
perature sensor
Check temperature sensor at ter-
minal S3 on the Vitosolic 100.
94
No solar DHW heating and, if
natural heat source is solar
thermal, no sorption opera-
tion
Short circuit, cylinder tem-
perature sensor
Check temperature sensor
%
on
the solar control module or temper-
ature sensor on the Vitosolic.
98
Control mode
Lead break, temperature
sensor
/
Check temperature sensor
/
on
the solar control module.
99
Control mode
Lead break, temperature
sensor
aÖ
Check sensor
aÖ
on solar control
module.
9A
No solar DHW heating and, if
natural heat source is solar
thermal, no sorption opera-
tion
Lead break, collector tem-
perature sensor
Check temperature sensor
&
on
solar control module or sensor on
the Vitosolic.
9b
Control mode
Lead break, cylinder tem-
perature sensor
Check temperature sensor at ter-
minal S3 on the Vitosolic 100.
9C
No solar DHW heating and, if
natural heat source is solar
thermal, no sorption opera-
tion
Lead break, cylinder tem-
perature sensor
Check temperature sensor
%
on
the solar control module or temper-
ature sensor on the Vitosolic.
Troubleshooting
Fault codes
(cont.)
5678 044 GB
Diagnosis
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...