155
Settings and test values
Set value
Commissioning Maintenance/
service
Date
Signature
Static pressure
mbar
kPa
≤
57.5
≤
5.75
Supply pressure (flow pressure)
=
for natural gas E
mbar
kPa
17-25
1.70-2.5
=
for natural gas LL
mbar
kPa
17-25
1.70-2.5
=
for LPG
mbar
kPa
42.5-57.5
4.25-5.75
Tick gas type
Carbon dioxide content CO
2
For natural gas
■
At lower heating output
% by vol.
7.5-9.5
■
At upper heating output
% by vol.
7.5-9.5
For LPG
■
At lower heating output
% by vol.
8.8-11.1
■
At upper heating output
% by vol.
8.8-11.1
Oxygen content O
2
■
At lower heating output
% by vol.
4.0-7.6
■
At upper heating output
% by vol.
4.0-7.6
Carbon monoxide content CO
■
At lower heating output
ppm
< 1000
■
At upper heating output
ppm
< 1000
Desiccant bag replaced during maintenance/service
Date
Signature
Commissioning/service reports
(cont.)
5678 044 GB
Appendix