72
Value, ad-
dress 00: ...
Description
9
1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2
(heating circuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), without DHW heating
(code is set automatically)
10
1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2
(heating circuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), with DHW heating (code
is set automatically)
Coding in the delivered condition
Possible change
11:0
No access to the coding addresses
for the parameters of the combus-
tion controller
11:9
Access to the coding addresses for
the parameters of the combustion
controller open
Note
Setting the code to "11:9" results in
the process circuit being cooled.
This can take approx. 20 min. Only
then is coding address "82" visible.
2A:0
Without wireless outside tempera-
ture sensor
2A:1
With wireless outside temperature
sensor (automatic recognition)
2A:2
Wireless outside temperature sensor
not used
2d:1
Never adjust
32:0
Without AM1 extension
32:1
With AM1 extension (automatic rec-
ognition)
33:1
Function of output A1 at AM1 ex-
tension: external heating circuit
pump (A1/HC1)
33:0
Function of output A1: DHW circula-
tion pump
33:2
Function of output A1: external cir-
culation pump for cylinder heating
34:0
Function of output A2 at AM1 ex-
tension: DHW circulation pump
34:1
Function of output A2: external heat-
ing circuit pump (A1/HC1)
34:2
Function of output A2: external cir-
culation pump for cylinder heating
35:0
Without EA1 extension
35:1
With EA1 extension (automatic rec-
ognition)
36:0
Function of output
aBJ
at EA1 ex-
tension: fault message
36:1
Function of output
aBJ
: feed pump
36:2
Function of output
aBJ
: DHW circu-
lation pump
3A:0
Function of input DE1 at EA1 ex-
tension: not assigned
3A:1
Function of input DE1: operating
program changeover
3A:2
Function of input DE1: external de-
mand with set flow temperature
Set flow temperature setting: coding
address 9b
Internal circulation pump function:
coding address 3F
3A:3
Function of input DE1: external
blocking
Internal circulation pump function:
coding address 3E
3A:4
Function of input DE1: external
blocking with fault message input
Code 2
"General"
(cont.)
5678 044 GB
Codes
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...