Fault code dis-
played
System characteristics
Cause
Measures
bE
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 3 (with mix-
er)
Check connections, cable, coding
address "A0" in the
"Heating cir-
cuit"
group and remote control set-
tings (see page 148).
With wireless remote controls:
check connection; place remote
control close to the heat source.
bF
Control mode
Incorrect LON communi-
cation module
Replace LON communication mod-
ule.
C1
Control mode
Communication error, EA1
extension
Check connections.
C2
Control mode
Communication error, so-
lar control module or
Vitosolic
Check solar control module or
Vitosolic.
C3
Control mode
Communication error,
AM1 extension
Check connections.
C4
Control mode
Communication error,
OpenTherm extension
Check OpenTherm extension.
C5
Control mode, max. pump
speed
Communication error, vari-
able speed secondary
pump
Check setting of coding address
"30" in the
"Boiler"
group.
Cd
Control mode
Communication error,
Vitocom 100 (KM-BUS)
Check connections, Vitocom 100,
type GSM2 and coding address
"95" in the
"General"
group.
CF
Control mode
Communication error,
LON communication mod-
ule
Check whether the LON communi-
cation module is correctly inserted.
Replace LON communication mod-
ule.
d6
Control mode
Input DE1 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
d7
Control mode
Input DE2 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
d8
Control mode
Input DE3 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
dA
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 1 (without mixer)
Check room temperature sensor,
heating circuit 1.
External room temperature sensor
for Vitotrol 300-A or integrated sen-
sor for Vitotrol 200-A/200-RF/
300-A/300-RF
db
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 2 (with mixer)
Check room temperature sensor,
heating circuit 2.
External room temperature sensor
for Vitotrol 300-A or integrated sen-
sor for Vitotrol 200-A/200-RF/300-
A/300-RF
dC
Control mode without room
influence
Short circuit, room tem-
perature sensor, heating
circuit 3 (with mixer)
Check room temperature sensor,
heating circuit 3.
External room temperature sensor
for Vitotrol 300-A or integrated sen-
sor for Vitotrol 200-A/200-RF/300-
A/300-RF
Troubleshooting
Fault codes
(cont.)
5678 044 GB
Diagnosis
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...