94
Fault code dis-
played
System characteristics
Cause
Measures
6A
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Fault in evaporator circuit
sensors 12 and 13
■
Check for air in the primary cir-
cuit and vent if required.
■
Check evaporator circuit sensors
12 and 13; replace if required.
6b
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Evaporator temperature
too low
If natural heat source is geother-
mal energy via geothermal probe:
■
Ground temperature too low. No
action required
If natural heat source is solar ther-
mal:
■
Check mixing valve
6C
No heating operation and no
DHW heating
Low temperature process
pump fault
Check low temperature process
pump cable and replace low tem-
perature process pump if necessa-
ry.
6D
No heating operation and no
DHW heating
High temperature process
pump fault
Check high temperature process
pump cable and replace high tem-
perature process pump if necessa-
ry.
6E
No heating operation and no
DHW heating
Control valve fault
Check control valve cable, motor
and ball valve, and replace if nec-
essary.
70
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Short circuit, evaporator
inlet temperature sensor
Replace evaporator inlet tempera-
ture sensor (for location, see
page 103)
71
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Lead break, evaporator in-
let temperature sensor
Replace evaporator inlet tempera-
ture sensor (for location, see
page 103)
72
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Short circuit, evaporator
outlet temperature sensor
Replace evaporator outlet temper-
ature sensor (for location, see
page 103)
73
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Lead break, evaporator
outlet temperature sensor
Replace evaporator outlet temper-
ature sensor (for location, see
page 103)
74
No heating operation and no
DHW heating
Short circuit, heat ex-
changer temperature sen-
sor
Replace heat exchanger tempera-
ture sensor.
75
No heating operation and no
DHW heating
Lead break, heat ex-
changer temperature sen-
sor
Replace heat exchanger tempera-
ture sensor.
76
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Short circuit, sorber outlet
temperature sensor
Replace sorber outlet temperature
sensor, plus process circuit flow
and return temperature sensors.
Start sensor calibration manually
(code "16:1" in the
"Process"
group).
77
No sorption operation; heat-
ing operation and DHW heat-
ing only in condensing mode
Lead break, sorber outlet
temperature sensor
Replace sorber outlet temperature
sensor, plus process circuit flow
and return temperature sensors.
Start sensor calibration manually
(code "16:1" in the
"Process"
group).
Troubleshooting
Fault codes
(cont.)
5678 044 GB
Diagnosis
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...