96
Fault code dis-
played
System characteristics
Cause
Measures
9E
Control mode
No flow rate in solar circuit
or flow rate too low, or
temperature limiter has re-
sponded.
Check solar circuit pump and solar
circuit. Acknowledge fault mes-
sage.
9F
Control mode
Solar control module or
Vitosolic fault
Replace solar control module or
Vitosolic.
A3
Burner blocked
Flue gas temperature sen-
sor incorrectly positioned
Fit flue gas temperature sensor
correctly (see page 107).
A7
Control mode with incorrect
time
Programming unit faulty
Replace the programming unit.
A8
Burner blocked. The venting
program is started automati-
cally (see page 43)
Air in the secondary pump
or minimum flow rate not
achieved
Vent the secondary circuit if the
fault message continues to be dis-
played.
A9
If a heating circuit with mixer
is connected, the burner op-
erates at its lower heating
output.
If only one heating circuit
without mixer is connected,
the burner is blocked.
Secondary pump blocked
Check secondary pump.
b0
Burner blocked
Short circuit, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
b1
Control mode as per deliv-
ered condition
Communication error, pro-
gramming unit
Check connections; replace pro-
gramming unit if necessary.
b5
Control mode as per deliv-
ered condition
Internal fault
Replace control unit.
b7
Burner blocked
Fault, coding card
Plug in coding card or replace if
faulty.
b8
Burner blocked
Lead break, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
bA
Mixer regulates to 20 °C flow
temperature.
Communication error, ex-
tension kit for heating cir-
cuit 2 (with mixer)
Check extension kit connections
and code.
bb
Mixer regulates to 20 °C flow
temperature.
Communication error, ex-
tension kit for heating cir-
cuit 3 (with mixer)
Check extension kit connections
and code.
bC
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 1 (without
mixer)
Check connections, cable, coding
address "A0" in the
"Heating cir-
cuit"
group and remote control set-
tings (see page 148).
With wireless remote controls:
check connection; place remote
control close to the heat source.
bd
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 2 (with mix-
er)
Check connections, cable, coding
address "A0" in the
"Heating cir-
cuit"
group and remote control set-
tings (see page 148).
With wireless remote controls:
check connection; place remote
control close to the heat source.
Troubleshooting
Fault codes
(cont.)
5678 044 GB
Diagnosis
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...