84
Coding in the delivered condition
Possible change
b2:8
With remote control and for the
heating circuit, operation with room
temperature hook-up must be pro-
grammed: room influence factor 8
(only change the code for the heat-
ing circuit with mixer)
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor adjustable
from 1 to 64. The higher the value,
the greater the room influence.
b5:0
With remote control: no room tem-
perature-dependent heating circuit
pump logic function (change code
only for heating circuit with mixer)
b5:1
to
b5:8
For heating circuit pump logic func-
tion, see the following table:
Parameter address
b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
> RT
set
RT
actual
< RT
set
–
1 K
7
RT
actual
> RT
set
–
1 K
RT
actual
< RT
set
–
2 K
8
RT
actual
> RT
set
–
2 K
RT
actual
< RT
set
–
3 K
Coding in the delivered condition
Possible change
C5:20
Electronic minimum flow tempera-
ture limit 20 °C
C5:1
to
C5:127
Minimum limit adjustable from 1 to
127 °C (limited by appliance-specific
parameters)
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
C6:10
to
C6:127
Maximum limit adjustable from 10 to
127 °C (limited by appliance-specific
parameters)
d3:8
Heating curve slope = 0.8
d3:2
to
d3:35
Heating curve slope adjustable from
0.2 to 3.5 (see page 59)
d4:0
Heating curve level = 0
d4:–13
to
d4:40
Heating curve level adjustable from
–
d5:0
External operating program
changeover switches the operating
program to "Constant operation at
reduced room temperature" or
"Standby mode"
d5:1
The external operating program
changeover switches to "Constant
operation at standard room tempera-
ture" (subject to coding addresses
"3A", "3b" and "3C")
d6:0
Heating circuit pump stays in con-
trol mode at "External blocking"
signal.
d6:1
Heating circuit pump stops at "Exter-
nal blocking" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d6:2
Heating circuit pump starts at "Exter-
nal blocking" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
d7:0
Heating circuit pump stays in con-
trol mode at "External demand"
signal.
d7:1
Heating circuit pump stops at "Exter-
nal demand" signal (subject to cod-
ing addresses "3A", "3b" and "3C")
Code 2
"Heating circuit"
(cont.)
5678 044 GB
Codes
Summary of Contents for D2RA
Page 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Page 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Page 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Page 163: ...163 5678 044 GB ...