99
"Heating circuit 3"
Function
Code
Operat-
ing level
Setting options
Delivered
condition
"Room temperature
comfort setpoint"
1310
"E"
6 to 35 °C
20.0
"Room temperature re-
duced setpoint"
1312
"E"
6 to 35 °C
14.0
"Room temperature frost
protection setpoint"
1314
"E"
4 to 35 °C
4.0
"Heating curve slope"
(see page 81)
1320
"F1"
0.10 to 4.00
1.40
"Heating curve displace-
ment"
(see page 81)
1321
"F1"
- 4.5 to 4.5 °C
0.0
"Summer/winter heating
limit"
1330
"F1"
- - -/8 to 30 °C
18
"24-hour heating limit"
(see page 159)
1332
"F2"
- - -/- 10 to 10 °C
0
"Flow temp setpoint
min"
1340
"F2"
8 to 95 °C
20
"Flow temp setpoint
max"
1341
"F2"
8 to 95 °C
80
"Room temperature in-
fluencing factor"
1350
"F2"
- - -/0 to 100 %
0
"Type room controller"
(see page 160)
1359
"F2"
■
"Manually"
■
"Radiator
fast"
■
"Radiator me-
dium"
■
"Radiator
slow"
■
"Floor heat
fast"
■
"Floor heat
medium"
■
"Floor heat
slow"
"Radiator
medium"
"Room temp limitation"
1360
"F2"
- - -/0.5 to 4.0 °C
2.0
Codes
Changing codes
(cont.)
5618 294 GB
Service
Summary of Contents for C3HA
Page 39: ...39 2 2x 1 Installation sequence Removing the front panel 5618 294 GB Installation ...
Page 42: ...42 1 2 Installation sequence Removing the transport brackets 5618 294 GB ...
Page 151: ...151 Checking and replacing resistors B C A Troubleshooting Repairs cont 5618 294 GB Service ...
Page 181: ...181 Parts lists Control unit assembly cont 5618 294 GB Service ...
Page 183: ...183 Parts lists Miscellaneous assembly cont 5618 294 GB Service ...
Page 191: ...191 5618 294 GB ...