Checking the temperature limiter
If the burner control unit cannot be reset
after a fault shutdown even though the
boiler water temperature is below
approx. 75 °C, check the following:
A
1.
Pull the cables from thermal circuit
breaker
A
.
2.
Check the continuity of the thermal
circuit breaker with a multimeter.
3.
Remove the faulty thermal circuit
breaker.
4.
Fit a new thermal circuit breaker and
connect cables.
Troubleshooting
Repairs
(cont.)