110
Function
Code
Operat-
ing level
Setting options
Delivered
condition
"Cont type input EX2"
■ NC: Contact closed,
must be opened to acti-
vate
■ NO: Contact open, must
be closed to activate
5983
"F2"
■
"NC"
■
"NO"
"NO"
"Readjustm outside sen-
sor"
(outside temperature
sensor)
6100
"F2"
- 3 to 3 °C
0
"Saving sensors"
If "Yes" is set, the current
status of the sensor inputs
is saved (e.g after remov-
ing a sensor). This status is
then not recorded as a fault
when the sensors are
checked on a daily basis at
0:00 h.
6200
"F2"
■
"No"
■
"Yes"
"No"
"Save parameters"
If "Yes" is set, the current
parameter settings are
saved as new default set-
tings.
The factory set-
tings are thus overrid-
den.
This does not include
fields such as time and
date, programming unit,
wireless, service/special
operation, all time pro-
grams and metering func-
tions.
6204
"F2"
■
"No"
■
"Yes"
"No"
Codes
Changing codes
(cont.)
5618 294 GB