66
Wobbe index ranges
Gas type
Wobbe index range
kWh/m
3
MJ/m
3
Delivered condition
Natural gas E
or
12.0 to 16.1
43.2 to 58.0
Natural gas LL
10.0 to 13.1
36.0 to 47.2
Converting the gas type
Replace the gas restrictors on both burn-
ers. The gas restrictors are packed sep-
arately and shipped with the boiler.
Gas restrictor assignment
Gas type
Burner
Identification
Drilled hole
7
mm
Natural gas E
Stirling
39
3.9
Auxiliary
37
3.7
Natural gas LL Stirling
44
4.4
Auxiliary
42
4.2
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)