Re-install the magnet valve with the old seal (SW 30). Note the tight-
ening torque of the union nuts: max. 8 Nm.
NOTICE! Risk of damage to magnet valve! Do not forget to
put the sieve back in again to avoid damage to the valve due
to dirt particles!
Fill and flush the system.
3.3.5
Manual functional test
We recommend to do a manual functional test after completion of
installation or in case of fault.
At the start of the functional test, only the central LED emits light
(
„Function“ ). The following components are queried:
n
Magnet valve
n
Flow switch
n
Backflow sensor
Flushing with all four sections must take place correctly, without back-
flow and with indication that flowthrough is present.
Enable all four valves (= delivery state).
Check the proper connection of drinking water and wastewater.
Press the Test button and keep pressed until all four valve sections
are open (LED indication).
ð
The flowthrough indicator emits light, the backflow indicator
does not light up.
Release the Test button.
ð
The valves close automatically with a time delay.
Next, set the valves / flowthrough volume to the correct values.
Chapter 3.5.2 „Troubleshooting“
During the test flushing, the LEDs emit light as follows:
n
LED
„Function“ emits light permanently
n
LED valve 1 lights up.
n
LED valve 2 lights up.
n
LED valve 3 lights up.
n
etc.
Description
Execution
LED indications
Handling
Flush valve universal
40 from 62