1
2
3
4
Fig. 5: Overview siphon
1 - lid
2 - socket
3 - drain with free discharge AB
4 - floating switch
2.3.2
Operating mode
The flush valve is intended for automated water exchange (flushing) in
the connected drinking water pipelines. The flush valve is suitable for
connection to DN 12-80 manifold or riser pipes.
One flush valve each regulates the water exchange in the cold water
and hot water pipes.
The flush valve can be placed in the following spots:
n
at the end of the pipeline run
n
at the end of the manifold lines
n
in the supply line to the fire extinguishing systems
n
In the supply line to rarely used sections of the installation.
Siphon
Placement
Product information
Flush valve universal
12 from 62