NOTICE!
The maximum load on the binary outputs is 24 V and 1 A
(max. 24 W). Do not switch loads directly via the signal out-
puts!
An analog voltage of 6–48 V AC/DC can be applied at connector 8 to
initiate a water exchange.
NOTICE!
Load the analog voltage input with minimum voltage, e.g.
100 mA at 24 V (max. 3 W).
Example: 12 V and 250 mA
Connector 9 is an analog current output 4–20 mA.
Number in the
wiring diagram
Output mes-
sage
Contact closed
Contact open
- 4 -
Fault or oper-
ating
Normal opera-
tion
Control current-
less, magnet
valve short-
circuited or
defective
- 6 -
Water
exchange
ongoing, or
leaks
Flowthrough
> 6 l/min
No flowthrough,
or flowthrough
< 6 l/min
- 7 -
Backflow
Backflow sensor
is triggered or is
defective
Normal opera-
tion
2.3.3
Sound protection
All components are mounted to the mounting bracket with acoustic
insulation.
We recommend to use acoustic insulation also when
mounting the base. Place for example a rubber mat or insu-
lation material between the brickwork and the base.
Product information
Flush valve universal
16 from 62