Parallel operation (appendix C)
Step 1: Setting ds2 and ds1 for parallel operation
The current settings (AC current limitation and charging current) are multiplied by the
number of devices. However, the AC current limitation setting when using a remote
panel will always correspond to the value indicated on the panel and is
not
multiplied
by the number of devices.
Example: 9kVA parallel system
- If an AC input current limit of 20A is set on the master and the system consists of three devices,
then the effective system current limit will be equal to 3 x 20 = 60A.
- If a 30A panel is connected to the master, the system current limit is adjustable to a maximum of
30A, regardless of the number of devices.
- If the charging current on the master is set to 100% (70A for a MultiPlus 24/3000/70) and the
system consists of three devices, then the effective system charging current is equal to 3 x 70 =
210A.
The settings according to this example (9kVA parallel system with 30A Multi Control Panel) are as
follows:
Master
Slave 1
Slave 2 (optional)
DS-8 AC input Set
DS-7 AC input Set
DS-6 AC input Set
DS-5 AES na
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
off
DS-1 Master
on
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
off
DS-1 Slave 2
on
Summary of Contents for MultiPlus 12/3000/120 - 50
Page 1: ...Manual EN Appendix MultiPlus 12 3000 120 50 120V 24 3000 70 50 120V ...
Page 2: ......
Page 4: ......
Page 50: ......
Page 51: ...EN Appendix www victronenergy com APPENDIX A Overview connections B H I J F E G A C K L ...
Page 53: ...EN Appendix www victronenergy com APPENDIX B Block diagram See table in section 4 2 ...
Page 58: ...APPENDIX G Dimensions ...
Page 59: ...EN Appendix www victronenergy com ...
Page 60: ......
Page 61: ...www victronenergy com ...