14
4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table.
12/3000/120
24/3000/70
48/3000/35
Recommended battery capacity (Ah)
400–1200
200–700
100–400
Recommended DC fuse
400A
300A
125A
Recommended cross section (mm
2
)
per + and - connection terminal
0 – 5 m
2x 50 mm
2
50 mm
2
35 mm
2
5 – 10 m
2x 70 mm
2
2x 50 mm
2
2x 35 mm
2
* ‘2x’ means two positive and two negative cables.
Remark: Internal resistance is the important factor when working with low capacity
batteries. Please consult your supplier or the relevant sections of our book “Energy
Unlimited”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
- Undo the four screws at the front of the enclosure and remove the front panel.
- Connect the battery cables: see Appendix A.
- Tighten the nuts well for minimal contact resistance.
Summary of Contents for MultiPlus 12/3000/120 - 50
Page 1: ...Manual EN Appendix MultiPlus 12 3000 120 50 120V 24 3000 70 50 120V ...
Page 2: ......
Page 4: ......
Page 50: ......
Page 51: ...EN Appendix www victronenergy com APPENDIX A Overview connections B H I J F E G A C K L ...
Page 53: ...EN Appendix www victronenergy com APPENDIX B Block diagram See table in section 4 2 ...
Page 58: ...APPENDIX G Dimensions ...
Page 59: ...EN Appendix www victronenergy com ...
Page 60: ......
Page 61: ...www victronenergy com ...