36
Step 2: Exemplary setting for 3-phase mode
In this example the leader is configured according to factory settings.
Leader (L1)
Follower (L2)
Follower (L3)
DS-8 Ch. Volt. GEL 14,4V
off
DS-7 Ch. Volt. GEL 14,4V
on
DS-6 Absorption time (8 h)
on
DS-5 Adaptive ch. (on)
on
DS-4 Dyn. current limit (off)
off
DS-3 UPS function (on)
on
DS-2 Voltage (120V)
on
DS-1 Frequency (60Hz)
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 D. c. l. (off)
off
DS-3 UPS f. (on)
on
DS-2 V (120V)
on
DS-1 na
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 D. c. l. (off)
off
DS-3 UPS f. (on)
on
DS-2 V (120V)
on
DS-1 na
To store the settings after the required values have been set: press the 'Down' button
of the
leader
for 2 seconds (
lower
button to the right of the DIP switches).
The
temperature and low-battery LED’s will flash to indicate acceptance of the
settings
.
You can then leave the DIP switches in the selected positions, so that the ’other
settings’ can always be recovered.
To start the system: first, turn all devices off. The system will start up as soon
as all devices have been turned on.
6. Maintenance
The MultiPlus does not require specific maintenance. It will suffice to check all
connections once a year. Avoid moisture and oil/soot/vapours, and keep the device
clean.
Summary of Contents for MultiPlus 12/3000/120 - 50
Page 1: ...Manual EN Appendix MultiPlus 12 3000 120 50 120V 24 3000 70 50 120V ...
Page 2: ......
Page 4: ......
Page 50: ......
Page 51: ...EN Appendix www victronenergy com APPENDIX A Overview connections B H I J F E G A C K L ...
Page 53: ...EN Appendix www victronenergy com APPENDIX B Block diagram See table in section 4 2 ...
Page 58: ...APPENDIX G Dimensions ...
Page 59: ...EN Appendix www victronenergy com ...
Page 60: ......
Page 61: ...www victronenergy com ...