APPENDIX E: Charge characteristic
C h a rg e c u rre n t
0 %
2 0 %
4 0 %
6 0 %
8 0 %
1 0 0 %
1 2 0 %
T i m e
A m p s
C h a rg e v o lta g e
1 0
1 1
1 2
1 3
1 4
1 5
1 6
T i m e
V o l ts
4-stage charging:
Bulk
Entered when charger is started. Constant current is applied until nominal battery voltage is reached, depending on
temperature and input voltage, after which constant power is applied up to the point where excessive gassing is starting (14.4V
resp. 28.8V, temperature compensated).
Battery Safe
The applied voltage to the battery is raised gradually until the set Absorption voltage is reached. The Battery Safe Mode is part
of the calculated absorption time.
Absorption
The absorption period is dependent on the bulk period. The maximum absorption time is the set Maximum Absorption time.
Float
Float voltage is applied to keep the battery fully charged
Storage
After one day of float charge the output voltage is reduced to storage level. This is 13,2V resp. 26,4V (for 12V and 24V
charger). This will limit water loss to a minimum when the battery is stored for the winter season.
After an adjustable time (default = 7 days) the charger will enter Repeated Absorption-mode for
an adjustable time (default =
one hour) to ’refresh’ the battery.
Summary of Contents for MultiPlus 12/3000/120 - 50
Page 1: ...Manual EN Appendix MultiPlus 12 3000 120 50 120V 24 3000 70 50 120V ...
Page 2: ......
Page 4: ......
Page 50: ......
Page 51: ...EN Appendix www victronenergy com APPENDIX A Overview connections B H I J F E G A C K L ...
Page 53: ...EN Appendix www victronenergy com APPENDIX B Block diagram See table in section 4 2 ...
Page 58: ...APPENDIX G Dimensions ...
Page 59: ...EN Appendix www victronenergy com ...
Page 60: ......
Page 61: ...www victronenergy com ...