Master
Slave 1
Slave 2
DS-8 na (30A panel)
DS-7 na (30A panel)
DS-6 na (30A panel)
DS-5 AES na
DS-4 Ch. current 3x70A
on
DS-3 Ch. current 3x70A
on
DS-2 Master
off
DS-1 Master
on
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 1
off
DS-1 Slave 1
off
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slave 2
off
DS-1 Slave 2
on
To store the settings after the required values have been set: press the 'Up' button of the
master
for 2 seconds (
upper
button to the right of the DIP switches, see appendix A, position J).
The
overload and low-battery LED’s will flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).