28
DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel
or
3-phase operation
Stand-alone operation
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC input Set as desired
DS-7 AC input Set as desired
DS-6 AC input Set as desired
DS-5 AES Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
off
DS-1 Stand-alone operation
off
Examples of the other DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting
Note:
since factory settings are entered by computer, all DIP switches of a new product are set to
‘off’ and do not reflect the actual settings in the microprocessor.
Four examples of stand-alone settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
off
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 St.-alone mode
off
DS-1 St.-alone mode
off
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
on
DS-7
off
DS-6
on
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in: 50A
5 AES: off
4, 3 Charging current: 75%
2, 1 Stand-alone mode
Step1, stand-alone
Example 2:
8, 7, 6 AC-in: 50A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
Step1, stand-alone
Example 3:
8, 7, 6 AC-in: 30A
5 AES: off
4, 3 Charge: 100%
2, 1 Stand-alone
Step1, stand-alone
Example 4:
8, 7, 6 AC-in: 40A
5 AES: on
4, 3 Charge: 50%
2, 1 Stand-alone
To store the settings after the required values have been set: press the 'Up' button for 2 seconds
(upper button to the right of the DIP switches, see appendix A, position J). The overload and low-
battery LED’s will flash to indicate acceptance of the settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
Summary of Contents for MultiPlus 12/3000/120 - 50
Page 1: ...Manual EN Appendix MultiPlus 12 3000 120 50 120V 24 3000 70 50 120V ...
Page 2: ......
Page 4: ......
Page 50: ......
Page 51: ...EN Appendix www victronenergy com APPENDIX A Overview connections B H I J F E G A C K L ...
Page 53: ...EN Appendix www victronenergy com APPENDIX B Block diagram See table in section 4 2 ...
Page 58: ...APPENDIX G Dimensions ...
Page 59: ...EN Appendix www victronenergy com ...
Page 60: ......
Page 61: ...www victronenergy com ...