Function Parameter Table VD500 Series Inverter User Manual
- 84 -
Value
A3-00
Speed Loop
Proportion Gain 1
1~100
30
○
A3-01
Speed Loop
Integral Time 1
0.01s~10.00s
0.50s
○
A3-02
Switching
Frequency 1
0.00Hz~A6-05
5.00Hz
○
A3-03
Speed Loop
Proportion Gain 2
1~100
20
○
A3-04
Speed Loop
Integral Time 2
0.01s~10.00s
1.00s
○
A3-05
Switching
Frequency 2
A6-02~max frequency
10.00Hz
○
A3-06
Vector Control Slip
Compensation
Gain
20%~200%
100%
○
A3-07
Speed Loop Filter
Time Constant
0.000s~0.100s
0.000s
○
A3-09
Torque Upper Limit
Source in Speed
Control Mode
0: Coding A3-10 setting
1: AI1
2: AI2
3: AI3 (expansion card)
4: PULSE setting
5: Communication Setting
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
The full scale of option 1~7
corresponding F3-10
0
○
A3-10
Torque Upper Limit
Digital Setting in
Speed Control
Mode
0.0%~200.0%
150.0%
○
A3-13
Excitation
Regulation
Proportion Gain
0~60000
2000
○
A3-14
Excitation
Regulation Integral
Gain
0~60000
1300
○
A3-15
Torque Regulation
Proportion Gain
0~60000
2000
○
A3-16
Torque Regulation
Integral Gain
0~60000
1300
○
A3-17
Speed Loop
Proportion Integral
Unit’s digit: Integral separation
0
○