Parameter Description VD500 Series Inverter User Manual
- 140 -
Bus voltage (V on)
0x0002
Input terminal state
0x0004
Output terminal state
0x0008
PID given value (% flash)
0x0010
PID feedback value (% on)
0x0020
Torque set value (% on)
0x0040
Analog AI1 value (V on)
0x0080
Analog AI2 value (V on)
0x0100
Analog AI3 value (V on)
0x0200
HS pulse HDI frequency
0x0400
PLC & MS speed current stage
0x0800
Pulse count value
0x1000
User-defined speed 1 (set value)
0x2000
User-defined speed 2 (set value)
0x4000
If you want to show multiple parameters (switch by shift key display), only to input hexadecimal
addition results of that several parameter.
F7-05
The Second Line LED
Running Display
Parameters
0~15 corresponding bit0~bit15 of F7-03
16~31 corresponding bit0~bit15 of
F7-04
4
○
F7-06
The Second Line LED
Stop Display Parameters
0~13 corresponding bit0~bit13 of F7-05
1
○
When use the double line show keyboard, can select a display value by these two parameters, but the
function is the decimal input.
F7-07
Load Speed Display
Coefficient
0.000s~6.5000
1.0000
○
F7-08
Load Speed Display
Decimal Places
0: 0 bit decimal place
1: 1 bit decimal place
2: 2 bit decimal place
3: 3 bit decimal place
1
○
When need to display the load speed, should adjust the corresponding relation of inverter output
frequency and load speed.
Below illustrates the calculation of load speed:
If load speed display coefficient F7-07 is 2.000, the load speed decimal digits F7-08 to 2 (two decimal
point), when inverter running frequency for 40.00Hz, load speed is: 40.00*2.000=80.00 (two decimal
point display).
If the inverter in a stop state, the load speed display for set frequency corresponding to the speed,
namely “setting load speed”. At a set frequency of 50.00Hz for example, the stop state load speed is:
50.00*2.000=100.00 (two decimal point display).