VD500 Series Inverter User Manual Function Parameter Table
- 47 -
F1-27
Acceleration/Decel
eration Mode
0: Straight-line
acceleration/deceleration
1: S curve acceleration/deceleration A
2: S curve acceleration/deceleration B
0
◎
F1-28
Time Ratio of S
Curve Start
Segment
0.0%~
(
100.0%-F1-26
)
30.0%
◎
F1-29
Time Ratio of S
Curve End
Segment
0.0%~
(
100.0%-F1-25
)
30.0%
◎
F1-30
Zero Frequency
Voltage Output
Selection
0: Have voltage output
1: Non voltage output
0
○
F2 Motor 1 Parameter
Function
Code
Parameter Name
Setting Range
Factory
Default
Value
Property
F2-00
Motor Type
Selection
0: Ordinary asynchronous motor
1: Frequency conversion
asynchronous motor
0
◎
F2-01
Rated Motor
Power
0.1kW~1000.0kW
Model
depende
nt
◎
F2-02
Rated Motor
Voltage
1V~2000V
Model
depende
nt
◎
F2-03
Rated Motor
Current
0.01A~655.35A (Inverter
power≤55kW)
0.1A~6553.5A (Inverter power>55kW)
Model
depende
nt
◎
F2-04
Rated Motor
Frequency
0.01Hz~max frequency
Model
depende
nt
◎
F2-05
Rated Motor
Rotation Speed
1RPM~65535RPM
Model
depende
nt
◎
F2-06
Asynchronous
Motor Stator
Resistance
0.001Ω~65.535Ω (Inverter
power≤55kW)
0.0001Ω~6.5535Ω (Inverter
power>55kW)
Tune
paramete
r
◎
F2-07
Asynchronous
Motor Rotor
Resistance
0.001Ω~65.535Ω (Inverter
power≤55kW)
0.0001Ω~6.5535Ω (Inverter
power>55kW)
Tune
paramete
r
◎